Front Terminal High Temperature Battery
download battery model full details here
DOWNLOAD PDFHigh temperature environment (35 C) °
Outdoor base station
Floating operation site
UPS
Nominal Voltage | 12 V |
Capacity | 100 Ah @10hr to 1.80 V per cell @ 25˚C(77˚F) 103 Ah @10hr to 1.80 V per cell @ 35˚C(95˚F) |
Weight | 31.5kg ( 69.45 lbs) |
Dimensions | Length: 395 mm (15.55 in) Width: 110 mm (4.33 in) Height: 286 mm (11.26 in) |
Internal Resistance (full charged) | 4.3 mΩ |
Short- circuit Current | 2122 A |
Self Discharge @ 35˚C(95˚F) | Less than 4% after 30 days storage |
Operating Temperature Range | Discharge: -40˚C ~ 65˚C(-40˚F~ 149˚F) Charge: -20˚C ~ 45˚C(-4˚F~ 113˚F) Storage: -20˚C ~ 40˚C(-4˚F~ 104˚F) |
Recommended Operating Temperature | 15˚C ~ 35˚C(59˚F~ 95˚F) |
Recommended Charging Current | 20 A |
Charging Voltage @35˚C(95˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M6 |
Container Materials | High Temp ABS /High Temp ABS V0(Optional) |
Capacity Affected by Temperature(c10) | 105% @ 40˚C(104˚F) 85% @ 0˚C(32˚F) 60% @ -20˚C(-4˚F) |
Design Life @35°C(95˚F) | 10 years |
F.V/Time |
| |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|
F.V/Time |
| |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|