Front Terminal High Temperature Battery
download battery model full details here
DOWNLOAD PDFHigh temperature environment (35 C) °
Outdoor base station
Floating operation site
UPS
Nominal Voltage | 12 |
Capacity | 170 Ah @10hr to 1.80V per cell @ 25˚C(77˚F) 175 Ah @10hr to 1.80V per cell @ 35˚C(95˚F) |
Weight | 57.5kg(126.77Ibs) |
Dimensions | Length: 559mm (22.00 in) Width: 125 mm (4.92in) Height: 315mm (12.40 in) |
Internal Resistance (full charged) | 3.2mΩ |
Short- circuit Current | 2852 A |
Self Discharge @ 35˚C(95˚F) | Less than 4 % after 30 days storage |
Operating Temperature Range | Discharge: -40˚C~ 65˚C(-40˚F~ 149˚F) Charge: -20˚C~ 45˚C(-4˚F~ 113˚F) Storage: -20˚C~ 40˚C(-4˚F~ 104˚F) |
Recommended Operating Temperature | 15˚C~ 35˚C(59˚F~ 95˚F) |
Recommended Charging Current | 34 A |
Charging Voltage @35˚C(95˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M6 |
Container Materials | High Temp ABS/High Temp ABS V0 (Optional) |
Capacity Affected by Temperature(c10) | 105% @ 40˚C(104˚F) 85% @ 0˚C(32˚F) 60% @ -20˚C(-4˚F) |
Design Life @35°C(95˚F) | 10 years |
F.V/Time |
| |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|
F.V/Time |
| |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|