Nominal Voltage | 2 V |
Capacity | 1000 Ah @ 10hr to 1.80 V @ 25˚C(77˚F) |
Weight | 56.5 kg (124.56 lbs) |
Dimensions | Length: 370 mm (14.57 in) Width: 181 mm (7.13 in) Height: 346 mm (13.62 in) Total height: 365 mm (14.37 in) |
Internal Resistance (full charged) | 0.36 mΩ |
Short- circuit Current | 10010 A |
Self Discharge @25˚C(77˚F) | Less than 3% after 30 days storage |
Operating Temperature Range | Discharge: -40˚C ~ 50˚C(-40˚F~ 122˚F) Charge: -20˚C ~ 45˚C(-4˚F~ 113˚F) Storage: -20˚C ~ 40˚C(-4˚F~ 104˚F) |
Recommended Operating Temperature | 15˚C ~ 25˚C (59˚F~ 77˚F) |
Recommended Charging Current | 150 A |
Charging Voltage @25˚C(77˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M8 |
Container Materials | ABS/ABS V0 (Optional) |
Capacity Affected by Temperature(C10) | 106% @ 40˚C(104˚F) 80% @ 0˚C(32˚F) 50% @ -20˚C(-4˚F) |
Design life @25°C(77˚F) | 15 years |
F.V/Time |
| ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
|
|