Nominal Voltage | 2 V |
Capacity | 600 Ah @ 10hr to 1.80 V @25˚C(77˚F) |
Weight | 46.5 kg (102.51 lbs) |
Dimensions | Length:145 mm(5.71 in) Width:206 mm(8.11 in) Height:645 mm(25.39 in) Total height:677 mm(26.65 in) |
Internal Resistance (full charged) | 0.35 mΩ @ 25˚C(77˚F) |
Short- circuit Current | 5706 A |
Self Discharge @25˚C(77˚F) | Less than 30% after 180 days storage |
Operating Temperature Range | Discharge: -20˚C~ 50˚C(-4˚F~ 122˚F) Charge: -20˚C~ 50˚C(-4˚F~ 122˚F) Storage: 5˚C~ 40˚C(41˚F~ 104˚F) |
Recommended Operating Temperature | 20˚C~ 25˚C (68˚F~ 77˚F) |
Recommended Charging Current | 90 A |
Charging Voltage @25˚C(77˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M10 |
Container Materials | ABS/ABS V0 (Optional) |
Capacity Affected by Temperature(C10) | 105%@ 40˚C(104˚F) 74%@ 0˚C(32˚F) 50%@ -20˚C(-40˚F) |
Design life @25°C(77˚F) | 20 years |
F.V/Time |
| |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|