download battery model full details here
DOWNLOAD PDFBack-up power for communication and signal system
Back-up power for Electric power system & nuclear power station
Back-up power for military & navigation
Back-up power for UPS & emergency lighting
Fire alarm and security system
Normal Voltage | 12V |
Capacity | 200 Ah @ 10hr to 1.80V per cell @ 25℃(77℉) |
Weight | Approx. 62kg (136.4lbs) |
Dimensions | Length:496mm Width:259mm Height:210mm Total Height:220mm |
Internal Resistance (full charged) | Approx. 3.7mΩ@ 25℃(77℉) |
Maximum Discharge Current | 1240A (5sec) |
Self Discharge @ 25℃ (77℉) | Less than 8 % after 90 days storage |
Operating Temperature Range | Discharge: -40℃~50℃(-40℉~122℉) Charge: -20℃~45℃(-4℉~113℉) Storage: -20℃~40℃(4℉~104℉) |
Recommended Operating Temperature | 15℃~25℃(59℉~77℉) |
Maximum Charging Current Limited | 40A |
Charging Voltage @25˚C(77˚F) | Float: 2.25 V/cell, Temps coefficient -3 mV/℃ Cycle: 2.35 V/cell |
Terminal | M8 |
Container Materials | ABS/ABS V0 (Optional) |
Capacity Aected by Temperature | 105 % @ 40℃ 85 % @ 0℃ 60 % @ -20℃ |
Design Life @25°C(77˚F) | 10 years |
F.V/Time |
| |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|
F.V/Time |
| |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|