VRLA Gel Battery
download battery model full details here
DOWNLOAD PDFDeep cycling energy storage application
Solar& wind energy storage system
Off-grid & bad-grid hybrid sites
Floating applications for telecom sites
Nominal Voltage | 2 V |
Capacity | 300 Ah @10hr to 1.80 V @ 25˚C(77˚F) |
Weight | 26.0 kg (57.3 lbs) |
Dimensions | Length:145 mm(5.71in) Width:206 mm(8.11in) Height:354 mm(13.94in) Total height:386 mm(15.20 in) |
Internal Resistance (full charged) | 0.47mΩ @ 25˚C(77˚F) |
Short- circuit Current | 4238 A |
Self Discharge @25˚C(77˚F) | Less than 30% after 180 days storage |
Operating Temperature Range | Discharge: -20˚C~ 50˚C(-4˚F~ 122˚F) Charge: -20˚C~ 50˚C(-4˚F~ 122˚F) Storage: 5˚C~ 40˚C(41˚F~ 104˚F) |
Recommended Operating Temperature | 20˚C~ 25˚C (68˚F~ 77˚F) |
Recommended Charging Current | 45 A |
Charging Voltage @25˚C(77˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M10 |
Container Materials | ABS/ABS V0 (Optional) |
Capacity Affected by Temperature(C10) | 105 %@ 40˚C(104˚F) 74 %@ 0˚C(32˚F) 50 %@ -20˚C(-40˚F) |
Design life @25°C(77˚F) | 20 years |
F.V/Time |
| |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|
F.V/Time |
| |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
|